Duct sensor for measuring relative and absolute humidity, enthalpy, dew point and temperature in gaseous media of heating, ventilation and air-conditioning systems as well as clean rooms. The optional features, such as relay outputs for 2-point controllers or 2-stage 2-point controllers and color-changing LCD allow for a wide range of applications. The accuracy of the humidity sensor is 2%. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation.
• Application/type : Duct sensor
• Purpose : Measure values
• Measured values : temperature, relative humidity, absolute humidity, enthalpy, dew point
• Interface : Passive, Active, 0..5 V, 0..10 V, 4..20 mA, Switch contact
• Configuration : USEapp, uConfig, jumper
• Sensor : Pt1000 DIN cl. B, Pt100 DIN cl. B, Pt1000 1/3 DIN, Pt100 1/3 DIN, Ni1000 DIN cl. B, Ni1000TK5000, NTC10k, NTC10k Precon, NTC20k, NTC1,8k, NTC5k, LM235Z, additional passive sensor
• Output voltage : 2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
• Output current : 2x 4..20 mA, max. load 500 Ω
• Output switch contact : 2x floating contact NO for 24 V ~ or 24 V = / 3 A
• Operating range temperature (°C) : -20..+70
• Output signal temperature : scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, adjustable at the transducer, optionally configurable, depending on used sensor
• Operating range humidity : max. 85% rH short term condensation