The maintenance-free and multi-functional duct air quality sensor measures CO2, mixed gas (VOC), temperature and humidity (relative, absolute, enthalpy, dew point). Optional features, such as a relay output for a 2-point controller or a 2-stage 2-point controller, LCD and traffic light function allow for a wide range of applications. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation.
• Application/type : Duct sensor
• Purpose : Measure values
• Measured values : temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2, VOC, CO2/VOC mix
• Interface : RS485 BACnet, Active, 0..5 V, 0..10 V
• Configuration : USEapp, uConfig, BUS, jumper, DIP switches, each output can be set to get a variable mix of CO2 and VOC by configuration via app or uConfig
• Sensor : NDIR (non-dispersive, infrared)
• Output voltage : 0..10 V or 0..5 V, 2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
• Network technology : RS485 BACnet (MS/TP)
• Operating range temperature (°C) : 0..+50
• Output signal temperature : scaling analogue output, 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable
• Operating range humidity : max. 85% rH short term condensation
• Accuracy temperature : ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
• Measuring range humidity : 0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable