Duct sensor for measuring air temperature and other gaseous media (e.g. in ventilation and air conditioning systems). Combined with a thermowell pocket, it can be used as an immersion temperature sensor as well. Models with a relay output for a 2-point controller or a 2-stage 2-point controller and color-changing LCD allow for a wide range of applications. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation.
• Application/type : Duct sensor, Immersion sensor
• Purpose : Measure values
• Measured values : temperature
• Interface : RS485 Modbus, Active, 0..5 V, 0..10 V
• Configuration : USEapp, uConfig, BUS, jumper, DIP switches
• Sensor : SI-Protection against permeation of humidity and mechanical stress (e.g. vibration)
• Output voltage : 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
• Network technology : RS485 Modbus
• Data transmission : RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit)
• Operating range temperature (°C) : -50..+160
• Operating ranges temperature (°C) : -50..+160
• Output signal temperature : scaling analogue output, 0..+160 °C (default setting), -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable
• Operating range temperature enclosure (°C) : -30..+70, -20..+70
• Operating range humidity : max. 85% rH short term condensation
• Accuracy temperature : ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig