Duct sensor for measuring the average temperature in air ducts. The sensor measures the mean temperature value throughout the entire length. A spring at the connection head reduces vibrations. Mounting angles are included in the delivery content. Models with a relay output for a 2-point controller or a 2-stage 2-point controller and color-changing LCD allow for a wide range of applications. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation.
• Application/type : Duct averaging sensor
• Purpose : Measure values
• Measured values : temperature
• Interface : RS485 BACnet, Active, 0..5 V, 0..10 V
• Configuration : USEapp, uConfig, BUS, jumper, DIP switches
• Output voltage : 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
• Network technology : RS485 BACnet (MS/TP)
• Operating range temperature (°C) : -30..+70
• Operating ranges temperature (°C) : 0..+50, -30..+70
• Output signal temperature : scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable via app or uConfig
• Operating range temperature enclosure (°C) : -30..+70, -20..+70
• Operating range humidity : max. 85% rH short term condensation
• Accuracy temperature : ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
• Power supply : 15..35 V = SELV, 19..29 V ~ SELV
• Power consumption : max. 2,5 W (24 V =), 4,3 VA (24 V ~)