Pendulum sensor for temperature measurement in large, high rooms and spaces like open space offices, arcades, production plants. Especially designed for control and display systems.
• Application/type : Pendulum sensor, Room sensor
• Purpose : Measure values
• Measured values : temperature
• Interface : RS485 BACnet
• Configuration : USEapp, uConfig, BUS
• Sensor : SI-Protection against permeation of humidity and mechanical stress (e.g. vibration)
• Output voltage : 0..10 V or 0..5 V, min. load 5 kΩ
• Network technology : RS485 BACnet (MS/TP)
• Operating range temperature (°C) : -35..+70
• Output signal temperature : scaling analogue output, 0..+160 °C (default setting), -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable via app or uConfig
• Operating range humidity : max. 85% rH short term condensation
• Accuracy temperature : ±0,5 K (typ. at 21 °C), within default measuring range
• Power supply : 15..35 V = SELV, 19..29 V ~ SELV
• Power consumption : typ. 2,5 W (24 V =), 4,3 VA (24 V ~)
• Material in touch with media : Sensor probe, Ø=15 mm, stainless steel V2A (1.4305), length 100 mm, hex pressed (IP65)
• Display : LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig
• Enclosure : USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
• Colour : pure white
• Protection (IP) : IP65, according to EN 60529