Cable sensor for temperature measurement in HVAC applications. Depending on the application requirements, different PVC, silicone and PTFE cables are available. The TF14 with its 4 mm diameter pocket is well suited for fast response applications.
• Application/type : Cable sensor
• Purpose : Measure values
• Measured values : temperature
• Interface : Passive
• Sensor : SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), Pt1000 DIN cl. B, Pt100 DIN cl. B, Pt1000 1/3 DIN, Pt100 1/3 DIN, Ni1000 DIN cl. B, Ni1000TK5000, NTC10k, NTC10k Precon, NTC10k Carel, NTC20k, NTC1,8k, NTC5k, passive
• Operating range temperature (°C) : -80..+250
• Operating ranges temperature (°C) : -35..+100, -50..+150, -50..+180, -80..+250
• Accuracy temperature : ±0,1 K (typ. at 0 °C), ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C), ±0,2 K (typ. at 25 °C, temperature dependend), ±0,3 K (typ. at 25 °C, temperature dependend), see characteristic curve
• Material in touch with media : Sensor probe, Ø=4 mm, stainless steel V4A (1.4571), 16-point pressed (IP65), rolled (IP67)
• Installation length (mm) : 50, 100, 150
• Enclosure : USE-S, impact- and shock-resistant enclosure with quick-release cover, PC
• Colour : pure white
• Protection (IP) : IP65, IP67, enclosure IP65, according to EN 60529
• Connection : removable cable entry flextherm M20 for wire Ø=4,5..9 mm, plug-in terminal, max. 2,5 mm²
• Connection cable : PVC, silicone, PTFE, 0,14 mm², 2-wire, 3-wire, 4-wire
• Length connection wire (m) : 1, 2, 4, 6
• Delivery content : incl. mounting base enclosure USE-S pure white, incl. fixing kit rawlplugs and screws (2x each)