CircuitSolver® is a self-actuating thermostatic balancing valve that automatically and continuously maintains a set water temperature at the end of each domestic hot water supply in a recirculation system. It solves the problem of delayed hot water delivery while completely eliminating the need for
time-consuming and expensive manual balancing.
The Problem
Many buildings require multiple branches off the hot water supply line.
Water flows to the path of least resistance.
Hot water use is hyper-dynamic, so the path of least resistance constantly changes.
Manual flow control valves cannot efficiently resolve these issues.
The Solution
Install a CircuitSolver® thermostatic balancing valve on each hot water supply branch line in a recirculation system immediately downstream of the last runout to a hot tap to guarantee hot water availability at any hot water fixture in your building regardless of demand usage.
Operation
The CircuitSolver Thermostatic Balancing Recirculation Valve constantly compensates for the fact that water always flows to the path of least resistance. As water use constantly changes throughout a building that path of least resistance also changes. By installing a CircuitSolver® immediately downstream of the last hot water fixture on each hot water branch line before it tees into the common hot water return line, the temperature of the hot water distribution system stays perfectly balanced, automatically.
CircuitSolver® opens when the water temperature drops below the set-point of the valves.