Level relay by conductive probes, for well or tank control.
- Very narrow: 18mm
- Adjustable sensitivity
- Minimum and maximum level probes
Codes and references
- 10000063 UH1-230
- 10001442 UH1-400
Specifications
- Signalling: VOLTAGE and RELAY
- Supply voltage: 230 Vac - 50 Hz (other voltages on request)
- Power consumption: 2 VA
- Permissible voltage variations: +10% -20%.
- Temperature range: -10º +60º C
- Response sensitivity: Adjustable 3...60 Kohms
- Probe voltage: 12 VAC. 50 Hz
- Probe current: 1.2 mA max. on short circuit
- Maximum terminal cross-section: 2 x 2.5 mm².
- Use of contacts: 2 A - 250 V~
- Approx. average weight: 85g
- Mounting: DIN 35 rail