Our production line includes single or double pole supporting type voltage transformers for indoor installation.
They contain up to three windings for revenue metering and protection purposes. An extra 100/3 V winding can be
provided in case the earth fault detection is demanded. Their cores are constructed from high quality siliceoussteel
laminations. All active parts are altogether impregnated with cycloaliphatic outdoor resin. If an additional ratio is
requested, thiscan be achieved by an intermediate terminal at the secondary coil or an additional coil. Each
terminal of the secondary coil can be grounded individually directly to the metal base through a bolt. These types
aremaintenance free,and with respect to their main dimensions many types correspond to the German standards
DIN 42600.
Highest voltage for eqwpmet (kV) 12 ZU 36
Rated insulation level [kV) 12/28/75 24/50/125 36/70/170
Rated primary voltage (V) from 30CMW3 up to 30000/V3
Rated secondary voltage (V] 100A/3 or 110/V3
Secondary tap upon request
Accuracy class 02:0.5:1:3
Rated burden of measuring winding (VA) 15 up to 120
Rated voltage of open delta winding (V) 100/3 or 110/3
Accuracy class 3P:6P
Rated burden of open delta winding (VA) 15 up to 100
Continuous thermal current of secondary winding (Al 6
Continuous thermal current of tertiary winding (A) 8
Rated voltage factor and permissible duration 1.9xUn/8h
Class of insulation E
Rated frequency (Hz) 162/3;50;60
Weight (kg) 18 26 33
Cantilever strength (N) >5000
Maximum altitude of installation (m) up to 1000
Ambient temperature (°Q - 5 up to + 50
Specifications IEC 61869-1 & 3: DIN ¿2600; ANSI: BS etc.