IP55 fan THGT series
axialextraction

IP55 fan - THGT series - Ventur - axial / extraction
IP55 fan - THGT series - Ventur - axial / extraction
IP55 fan - THGT series - Ventur - axial / extraction - image - 2
IP55 fan - THGT series - Ventur - axial / extraction - image - 3
IP55 fan - THGT series - Ventur - axial / extraction - image - 4
IP55 fan - THGT series - Ventur - axial / extraction - image - 5
IP55 fan - THGT series - Ventur - axial / extraction - image - 6
Add to favorites
Compare this product
 

Characteristics

Type
IP55
Configuration
axial
Function
extraction
Air flow

Min.: 1,438 m³/h
(50,782.491 ft³/h)

Max.: 109,435 m³/h
(3,864,660.553 ft³/h)

Description

General information Range of adjustable pitch cased axial flow fans designed for smoke extraction in conditions of combustion, and certified F400-120 and F200-120 (CE marked). Casings formed from rolled sheet steel with a corrosion resistant hot dipped galvanised finish.. All models incorporate separate high grade die-cast aluminum blades locked within a pressed sheet steel hub. All models are available in both short and long (L) casing versions (except 500 model). Suitable for use in both horizontal and vertical positions. Motors Available, depending on the model, with: three-phase motors in 2*, 4, 6 or 8 poles. three-phase two-speed motors 2/4*,4/8 or 6/12 poles. F400 120 motors are IP55, class H insulation. F200 120 motors are IP55, class F insulation. Electrical supplies: Three-phase 230/400V-50Hz up to 3 kW. Three-phase 400V-50Hz, for higher power motors and two-speed motors. *Only with F200-120 models

Catalogs

No catalogs are available for this product.

See all of Ventur‘s catalogs

Other Ventur products

Fans

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.