connection terminal plate, 3-pole
16 - 120 mm², AWG 2 - 250 MCM, lam. Cu. 9 - 15.5 x 2,4 - 10
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
System
60Classic
Product group - 07
Subgroup - 45
pack size - 1
EAN - 4021267012434
Advantages of the product
Terminals can be removed for connection of uncut conductors
catalog page - 2020 : 3.5
eCl@ss 6.1 - 27141146
eCl@ss 7.1 - 27141146
ETIM 4.0 - EC000001
ETIM 5.0 - EC000001
Details IEC
Standards
IEC 61439-1:2011
IEC 60999-1:1999
IEC 60999-2:2003
GB/T 7251.1
Electrical data IEC
Rated current (IEC): - 250 A
rated voltage (IEC) AC: - 690 V
rated surge voltage Uimp : - 6 kV
The insulation performance of the article depends on the installation conditions.
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 3.8 W.
(The power dissipation at full load would be 6 W.)
Supplementary data IEC
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.
max. permitted voltage (IEC) AC: - 1000 V
max. permitted voltage (IEC) DC: - 1500 V
current capacity (IEC) max.: - 440 A