Pressure tank setting requirements: Required not less than 2 liters inflatable pressure water tank (Preset pressure=60% of the setting pressure)
Other Parameters
■ Input power and voltage:
Three-phase AC power supply; 380VAC
■ Pressure tank setting requirements:
Required not less than 2 liters inflatable pressure water tank (Preset pressure=60% of the setting pressure)
■ Temperature range of this inverter and of the medium:
0~+40℃; Clean water within the temperature range of 0~+100℃
■ Required pressure when self-starting:
When the factory setting pressure is less than 0.3 bar
■ Notes for installation:
Make sure the grounding is appropriate and reliable before using.
■ Pressure sensor for those inverters:
24V, 4-20mA (10bar, 16bar, 25bar)
■ Allowed voltage fluctuation of those products:
80V~140V (110V) OR 160V~260V (220V) or 320V~450V (380v)